CS10-L Current Transducer
The CS10 uses CR Magnetic's CR8459 Current Transformer to measure the approximate current over a range of 0 to 200 Amps. The CS10 outputs a millivolt signal allowing the transducer to be directly connected to the CR510, CR10X, or CR23X dataloggers. The CS10-L is intended for lower-accuracy applications such as motor or generator load conditions, efficiency studies, intermittent fault detection, and rough submetering.
Features
Measures current from 0 to 200 Amps
Recommended for applications that do not require high accuracy
Specifications
Measurement Range: 0.15 to 200 A
Frequency: 50 and 60 Hz
Insulation Resistance: 100 M ohm @ 500 Vdc
High Potential: 2000 V
Rated Current: 200 A
Accuracy w/10 ohm Burden Max. (resistive): typically ±5% of actual value with provided multiplier
ACL1 Opto-Isolated AC Line Monitor
The ACL1 outputs a binary dc signal in response to the presence or absence of an ac voltage on the monitored line. An output that is less than 0.8 Vdc indicates no voltage; an output that is 3.7 to 5.1 Vdc indicates an active voltage.
Features
Monitors presence or absence of electrical ac power
CS15-L Current Transducer
The CS15 is a version of the CS10 optimized for use with the CR200-series dataloggers. It consists of a CR Magnetic's CR8459 Current Transformer modified to measure the approximate current over a range of 0 to 125 Amps.
The CS15 is recommended for measurements that do not require high accuracy, such as motor or generator load condition monitoring, efficiency studies, intermittent fault detection, and rough submetering.
Features
Measures current from 0 to 125 Amps
Recommended for applications that do not require high accuracy
Specifications
Measurement Range: 0.15 to 125 A
Frequency: 50 and 60 Hz
Insulation Resistance: 100 M ohm @ 500 Vdc
High Potential: 2000 V
Rated Current: 125 A
Accuracy w/10 ohm Burden Max. (resistive): typically ±5% of actual value with provided multiplier
Producing Area:USA