MDS-5 Data Logger

multi-channel data logger

  MDS-5 Data Logger            MDS-5 Data Logger

Special Features

analogue and digital input/output
connectors for any sensor type
possibility of event driven data acquisition
customer friendly installation and operation
low power consumption
high data storage capacity (480,000 values) and data security

MDS-5 Data Logger          MDS-5 Data Logger           

ground water - fountain house     flood monitoring

MDS-5 Data Logger                   MDS-5 Data Logger                             

surface water                            meteorological station

MDS-5/MDS-5 Com Data Loggers - Description

SEBA's newly designed MDS-5 multi-channel data logger is the successor of the well known and reliable data logger MDS. The
very compact MDS-5 logger stands out by its higher data storage capacity (480,000 values), improved data security and, in
particular, lower power consumption.
The MDS-5 is especially characterized by the following features:
     different operational registration modes: time-, dynamic- or event-contolled
     individual on/off control of attached sensors
     comprehensive alarm management with GSM/GPRS-modem incl. SMS messaging
The main and central component of the MDS-5 data logger is the independent CPU-unit with a serial flash-memory. In total up
to 12 sensors (8 analogue, 2 digital and other inputs) can be connected to this logger via user-friendly terminals. By default an
undisturbed and quick communication and data transfer is conducted by the RS232 or an USB-interface. Optional a bluetoothinterface
or modem module can be supplied.
The CPU board of the MDS-5 controls a CPU bus which links several CPU boards to one single-master unit / multi-slave.
Therefore, as an example, the data logger and the alarm management system can be set up with separate tasks.
The MDS-5 Com includes already an integrated GSM/GPRS-modem for data transmission.

Technical data MDS-5 and MDS-5 Com

protection class: IP40
power supply: 3.6V/7,2Ah lithium battery internal resp. 6...24V battery external
power consumption: standby: <50μA, activ: ca. 20mA
operation temperature: -20..+70°C
real time clock: RTC +/- 1min/month
interfaces: 1xRS232, 1xRS485, 1x USB
memory: 1MB serial flash memory (480,000 measuring values)
display: LC-display, 8-digits
key pad: 3x plastic foil key pad
AD-converter 16bit with input amplifier:
   max. 8 uni-polar channels (0...20mA resp. 0...2.5V)
   or 4 bi-polar channels (passive transducers)
   or mixed-up
2 impulse inputs, 1x BCD or 1x Graycode-
Measurement interval: 5s
Dimensions (WxHxD): 192mm x 105mm x 75mm
weight: ca. 700g

Optionally:
2x RS232-interface and 2x RS485-interface
Bluetooth-connection
integration of GSM/GPRS-Modem Type 740
digital output: galvanically isolated (alarm management)
analogue output: 4...20mA galvanically isolated (Online-channels)

Technical data of MDS-5, except
protection class: IP65
key pad: 1x foil key
Modem: internal GSM/GRPS (Type 74001) or telephone modem with antenna
inputs: serially via RS485 (max. 8 parameters)
alternatively: AD-converter 16bit with input amplifier:
                    max. 8 uni-polar channels (0…20mA resp. 0…2.5V) or 4 bi-polar channels (passive transducers) or mixed-up
                    2 impulse inputs

GSM/GPRS-Modem Type 740 (MDS-5)
GSM/GPRS-Modem Type 74001 (MDS-5 Com)

frequency:                       850/900MHz/1800/1900MHz (EGSM, Quadband)
HF output max.:              2W 850/ 900MHz
                                       1W 1800/1900MHz
antenna impedance:        50 Ohm
SIM-Card:                       1.8V / 3V / 5V
power supply:                 8VDC...12VDC
electric current:               100mA (receipt)
                                      30mA (standby)
                                      2.1A (transmission) max. 2.25A
operating temperature:   -30°C...85°C
storage temperature:      -40°C...85°C

MDS-5 Data Logger

Producing Area:Germany