SC100

The SC100 can work in a datalogger to sensor mode, or datalogger to computer mode. When used between a datalogger and a computer, the SC100 allows a CR10, CR10X, 21X, or CR23X to send Burst data to a computer. The SC100 typically receives Burst data from the datalogger at 78.6 kbaud, buffers it, then retransmits to the computer at 38.4 kbaud.
The SC100 can also filter and buffer data between a serial sensor and a CR10, CR10X, or 21X datalogger. It's used in applications where a sensor outputs serial ASCII data unconditionally or randomly. To read data sent from the SC100, the datalogger uses Instruction 15 and control ports. The SC100 buffers up to 90 bytes of serial data received at 1200, 2400, 4800, 9600, 19200, and 38400 bps then transmits the buffered data to the datalogger at 1200 bps. The data or commands can be transmitted from the datalogger to the sensor when required.

SC100

Features

Works between a datalogger and sensor (measurement and control), or datalogger and computer (communications)
Baud rates supported as a measurement and control peripheral: 1200, 2400, 4800, 9600, 19.2, and 38.4K
Operates in "Burst mode" as a communications peripheral
Performs buffering and baud rate conversion in both modes

Specifications

Power Source: Datalogger's 5 or 12 Vdc supply
Current Drain: 55 mA active, 50 μA quiescent

Producing Area:USA